            仿威圖機(jī)箱電氣柜成套怎樣才能更美觀?

            發(fā)布時(shí)間:2023-06-10 來源:http://m.landmann.cn/ 瀏覽量:

            1.折彎
            1. Bending
            所有的電線在敷設(shè)時(shí),都講究橫平豎直,配電箱也一樣。但是在配電箱接線中,雖然要求“直”,同時(shí)還要求不允許出現(xiàn)90°角。
            All wires should be laid horizontally and vertically, and the same applies to distribution boxes. However, in the wiring of the distribution box, although it is required to be "straight", it is also required that no 90 ° angle is allowed.
            這樣做是因?yàn)椋?dāng)電線的彎折角度大于90°后,就會(huì)對電線的絕緣層造成傷害——明顯的就是絕緣層發(fā)白、變色。后果就是降低絕緣層的耐性,對絕緣性、 阻燃性都有較大影響。
            This is because when the bending angle of the wire is greater than 90 °, it will cause damage to the insulation layer of the wire - the most obvious is the whitening and discoloration of the insulation layer. The consequence is to reduce the durability of the insulation layer, which has a significant impact on both insulation and flame retardancy.
            標(biāo)準(zhǔn)的做法是,所有需要折彎的地方,都折成圓弧形的角,同時(shí)還要保證縱向電線與橫向電線垂直。
            The standard practice is to fold all areas that need to be bent into circular corners, while also ensuring that the longitudinal wires are perpendicular to the transverse wires.
            2.交叉
            2. Intersection
            有兩種情況會(huì)出現(xiàn)交叉,種是沒有按照上文所說的,做到區(qū)分縱向的電線和橫向電線,更不用說保證兩者垂直了。當(dāng)電線亂七八糟的排列在配電箱里,勢必會(huì)造成電線較差。這樣做的后果是配電箱內(nèi)雜亂,一旦出現(xiàn)故障,維修起來會(huì)很麻煩。
            There are two situations where there may be intersections. The first is that the distinction between longitudinal and transverse wires has not been made as mentioned earlier, let alone ensuring that the two are perpendicular. When the wires are arranged in a disorderly manner in the distribution box, it is bound to cause poor wiring. The consequence of doing so is that the distribution box is messy, and once a malfunction occurs, it can be very troublesome to repair.
            另一種情況就比較嚴(yán)重了,是指橫平豎直的進(jìn)線與出線存在交叉。
            Another situation is more serious, which refers to the intersection of horizontal and vertical incoming and outgoing lines.
            在圖中,主開關(guān)的出線從開關(guān)的左側(cè)繞過,接到右側(cè)斷路器的上口。這樣一來,勢必會(huì)造成主開關(guān)的出線和主開關(guān)的進(jìn)線交叉。這樣做有兩個(gè)后果:①主開關(guān)的進(jìn)線會(huì)受到出線的壓迫,導(dǎo)致進(jìn)線接線不牢固;②在斷開主開關(guān)對配電箱進(jìn)行維修時(shí),維修人員就有可能在維修主開關(guān)出線時(shí)接觸到帶電的進(jìn)線,導(dǎo)致觸電。
            In the figure, the outgoing line of the main switch bypasses the left side of the switch and connects to the upper port of the right circuit breaker. In this way, it will inevitably cause the outgoing line of the main switch to cross with the incoming line of the main switch. There are two consequences of doing this: ① the incoming line of the main switch will be compressed by the outgoing line, resulting in unstable incoming wiring; ② When disconnecting the main switch for maintenance of the distribution box, maintenance personnel may come into contact with live incoming lines during the maintenance of the main switch outgoing line, resulting in electric shock.
            電氣成套
            3.跳線
            3. Jumper
            這個(gè)配電箱存在出線與進(jìn)線交叉的情況,這屬于上一節(jié)的內(nèi)容,不再多說。我們單看主開關(guān)的出線——主開關(guān)后面有四個(gè)分開關(guān),卻只從主開關(guān)的出線接線柱引出了2根線(零火線各一根)。那它是怎么為后面四個(gè)分開關(guān)提供電源的呢?(零線直接接到了零排上,我們不再管它。)
            This distribution box has a situation where the outgoing and incoming lines intersect, which belongs to the previous section and will not be further discussed. Let's just look at the outgoing lines of the main switch - there are four sub switches behind the main switch, but only two wires (one neutral wire and one live wire) are led out from the outgoing terminal of the main switch. How does it provide power for the following four sub switches? (The zero line is directly connected to the zero line, and we will no longer care about it.)
            方法是將出線接到個(gè)分開關(guān),再從個(gè)分開關(guān)的進(jìn)線接線柱引出一條線,接到第二個(gè)分開關(guān)……這樣一來,、二、三個(gè)分開管的上口接線柱,便都接了兩根線。這種從前一個(gè)斷路器上口取電源的方法,就叫做“跳線”。跳線的接法,早在2010年就被國標(biāo)禁止,原因如下。
            The method is to connect the outgoing line to the first sub switch, and then lead a line from the incoming terminal of the first sub switch to the second sub switch... In this way, the upper terminal of the first, second, and three separate pipes are all connected with two lines. This method of taking power from the previous circuit breaker is called "jumper". The connection of jumpers was prohibited by the national standard as early as 2010, for the following reasons.
            跳線的危害
            Hazards of Jumpers
            箱內(nèi)線,一般為4平方毫米或2.5平方毫米,4平方毫米的電線,大載流量為25A以上(數(shù)據(jù)來源于《GB/T 4706.1-2005》)。一個(gè)五孔插座的額定電流是10A,一個(gè)三孔插座的額定電流是16A,整個(gè)房間會(huì)有多少個(gè)插座?因此,25A的載流量很明顯不夠,是會(huì)引起電線過載的。
            The internal wire of the box is generally 4 square millimeters or 2.5 square millimeters, with a maximum current carrying capacity of 25A or more for wires of 4 square millimeters (data sourced from GB/T 4706.1-2005). The rated current of a five hole socket is 10A, and the rated current of a three hole socket is 16A. How many sockets will there be in the entire room? Therefore, the current carrying capacity of 25A is clearly insufficient and can cause wire overload.
            入戶線一般為6平方毫米,大載流量為32A以上,能夠滿足家用(因此要求家庭總開關(guān)的額定電流不超過32A)。
            The entrance line is generally 6 square millimeters, with a maximum current carrying capacity of 32A or above, which can meet the requirements of household use (therefore, the rated current of the home main switch should not exceed 32A).
            那么,如果我把箱內(nèi)電線換掉,也換成6平方毫米的行不行?答案是不行!電線太粗,勢必會(huì)擠壓箱內(nèi)空間,影響散熱。家用PZ30箱要求,電線不得超過4平方毫米。
            So, if I replace the wires inside the box, can I also replace them with 6 square millimeters? The answer is no! If the wires are too thick, they will inevitably squeeze the space inside the box and affect heat dissipation. Household PZ30 boxes require that the wires should not exceed 4 square millimeters.
            正確的接法為,每有一個(gè)支路斷路器,就要從主開關(guān)下口引出一條線。
            The correct connection method is to lead a line from the lower port of the main switch for each branch circuit breaker.
            本文由電氣成套友情奉獻(xiàn).更多有關(guān)的知識(shí)請點(diǎn)擊: http://m.landmann.cn 真誠的態(tài)度.為您提供為的服務(wù).更多有關(guān)的知識(shí)我們將會(huì)陸續(xù)向大家奉獻(xiàn).敬請期待.
            This article is dedicated to the friendship of electrical equipment. For more relevant knowledge, please click on: http://m.landmann.cn Sincere attitude. We will provide you with comprehensive services. We will gradually contribute more relevant knowledge to everyone. Stay tuned
            首頁首頁 產(chǎn)品產(chǎn)品 電話電話 置頂置頂
            主站蜘蛛池模板: 国产成人精品亚洲777| 国精品人妻无码一区免费视频电影| 夜爽8888视频在线观看| 人妻av无码系列一区二区三区| 99在线精品国自产拍不卡| 国产麻豆剧果冻传媒一区| 成a人片亚洲日本久久| 亚洲午夜精品av无码少妇| 亚洲香蕉免费有线视频| 欧美一区内射最近更新| 国产亚洲精品久久久久久无挡照片| 久久99精品久久99日本| 自拍偷自拍亚洲精品10p| 日韩亚洲精品国产第二页| 国产一区二三区日韩精品| 成人综合婷婷国产精品久久蜜臀| 正在播放少妇呻吟对白| 欧美日韩一线| 337p日本欧洲亚洲大胆精品| 亚洲精品无码久久千人斩| 黑人精品一区二区三区不| 精品无码av一区二区三区| 国产精品爽爽va在线观看无码| 尤物国产精品福利在线网| 丰满熟妇人妻中文字幕| 饥渴少妇av无码影片| 亚洲中文字幕在线二页| 伊人久久大香线焦av综合影院| 7777亚洲大胆裸体艺术全集 | 男人的天堂在线a无码| 91密桃精品国产91久久| 亚洲精品沙发午睡系列| 国产精品亚洲专区无码破解版| 国产精品自产在线观看一| 青草青草视频2免费观看| 欧洲美熟女乱又伦免费视频| 亚洲成在人线AV品善网好看| 麻豆一区二区三区久久| 久久久久无码精品国产人妻无码| 69精品丰满人妻无码视频a片| 国产精品后入内射视频|